7.6
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Inputs, Outputs, Timers, and Other Control Logic
Local Control Switches
Local Control Switches
The local control switch feature of this relay replaces traditional panel-
mounted control switches. Operate the sixteen (16) local control switches
using the front-panel keyboard/display (see
).
The switch representation in this figure is derived from the standard: Graphics
Symbols for Electrical and Electronics Diagrams IEEE Std 315-1975, CSA Z99-1975,
ANSI Y32.2-1975, 4.11 Combination Locking and Nonlocking Switch, Item 4.11.1.
Figure 7.4
Local Control Switches Drive Local Bits LB1 Through LB16
The output of the local control switch in
is a Relay Word bit LB
n
(
n
= 1 through 16), called a local bit. The local control switch logic in
repeats for each local bit LB1–LB16. Use these local bits in
SEL
OGIC
control equations. For a given local control switch, the local control
switch positions are enabled by making corresponding label settings.
Note the first setting in
n
) is the overall switch name setting.
Make each label setting through the serial port using the command
SET T
.
View these settings using the serial port command
SHO T
(see
Section 10: Serial Port Communications and
Local Control Switch
Types
Configure any local control switch as one of the following three switch types:
ON/OFF Switch
Local bit LB
n
is in either the ON (LB
n
= logical 1) or OFF (LB
n
= logical 0)
position.
Table 7.1
Correspondence Between Local Control Switch Positions and Label
Settings
Switch Position
Label Setting
Setting Definition
Logic State
not applicable
NLB
n
Name of Local
Control Switch
not applicable
ON
SLB
n
“Set” Local bit LB
n
logical 1
OFF
CLB
n
“Clear” Local bit LB
n
logical 0
MOMENTARY
PLB
n
“Pulse” Local bit LB
n
logical 1 for
one processing interval
Logical 1
LBn
(n = 1 through 16)
ON Position
(Maintained Logical 1 Position)
OFF Position
(Maintained Logical 0 Position)
MOMENTARY Position
(Logical 1 for One Processing Interval)
Relay
Word
Bit
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...