2.32
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Installation
AC/DC Connection Diagrams for Various Applications
Voltage must be applied between relay terminals
VA
and
N
(
Z09
and
Z12
, respectively) in order for the underfrequency
elements to operate. Make group setting VNOM = OFF to allow the undervoltage block for the frequency elements to
operate off one phase only (if only connecting one phase voltage to the relay).
The phase of the single-phase voltage connected to
VA-N
does not matter. For example, it could come from VB, VCA, or
from a station service transformer (suitably fused). It should come from the same bus section that the associated
breaker is connected, preferably from the “normally hot” side.
In the configuration shown, only nondirectional overcurrent protection is possible. The fault locator logic and the load
encroachment element are also disabled.
Voltage Channel VS does not need to be connected. Here, it is shown connected for use in voltage and synchronism
check elements and voltage metering. See
Synchronism Check VS Connection (Global Setting VSCONN = VS) on
Broken-Delta VS Connection (Global Setting VSCONN = 3V0) on page 2.14
Current Channel IN does not need to be connected. Channel IN provides current I
N
for the neutral ground overcurrent
elements. Separate from Channel IN, the residual ground overcurrent elements operate from the internally derived
residual current I
G
(I
G
= 3I
0
= I
A
+ I
B
+ I
C
). But, in this residual connection example, the neutral ground and residual
ground overcurrent elements operate the same because I
N
= I
G
.
Figure 2.23
Utility Distribution Feeder Underfrequency Load Shedding, Overcurrent Protection, and Reclosing
(Single Voltage Connection)
TC
Trip
Coil
52A
(+)
(—) Trip
Circuit
IA
C
B
A
N
VC
VB
SEL-351 RELAY
VA
OUT101
Forw
ar
d T
ripping Dir
ection
CC
Close
Coil
52B
(+)
(—) Close
Circuit
IB
OUT102
86
Lock
Out
86B
(+)
(—) Breaker
Failure
Trip
Circuit
TX
(—) Comm.-
Assisted
Trip
Scheme
IC
OUT103
IN
VS
NS
LINE
52
(+)
OUT104
(+)
52A
to Annunciator, RTU,
or SEL-2032/SEL-2030/SEL-2020
ALARM
(+)
(—)
Breaker Status
IN101
RX
(+)
(—) Comm.-Assisted
Trip Scheme
IN102
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...