5.31
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Trip and Target Logic
Front-Panel Target LEDs
Front-Panel Target LEDs
Target LEDs numbered 2 through 13 in
are updated and then latched
for every new assertion (rising edge) of the TRIP Relay Word bit. The TRIP
Relay Word bit is the output of the trip logic (see
).
Further target LED information follows. Refer also to
through
for the placement of the target LEDs on the front panel.
Additional Target LED
Information
TRIP Target LED
The
TRIP
target LED illuminates at the rising edge of trip (the new assertion of
the TRIP Relay Word bit).
The
TRIP
target LED is especially helpful in providing front-panel indication
for tripping that does not involve overcurrent or frequency elements. If the trip
is not an overcurrent or frequency element generated trip, none of the target
LEDs numbered 3 through 13 in
illuminate, but the
TRIP
target LED
still illuminates. Thus, tripping via the front-panel local control (local bits),
serial port (remote bits or
OPEN
command), or voltage elements is indicated
only by the illumination of the
TRIP
target LED.
Table 5.1
Front-Panel Target LED Definitions
LED
Number
LED
Label
Definition
1
EN
Relay Enabled—see
2
TRIP
Indication that a trip occurred, by overcurrent element,
frequency element, or otherwise
3
INST
Instantaneous trip
4
COMM
Communications-assisted trip
5
SOTF
Switch-onto-fault trip
6
50
Instantaneous/definite time overcurrent element generated trip
7
51
Time-overcurrent element generated trip
8
81
Frequency element generated trip
9
A
Phase A involved in the fault
10
B
Phase B involved in the fault
11
C
Phase C involved in the fault
12
G
Residual ground overcurrent element trips for the fault
13
N
Neutral ground overcurrent element trips for the fault
14
RS
Reclosing relay is in the Reset State
(follows Relay Word bit 79RS)
15
CY
Reclosing relay is in the Cycle State
(follows Relay Word bit 79CY)
16
LO
Reclosing relay is in the Lockout State
(follows Relay Word bit 79LO)
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...