I.7
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
M
IRRORED
B
ITS
(in Firmware Versions 6 and 7)
Settings
Mirrored Bits Receive Identifier(1-4) RXID = 1 ?
Mirrored Bits Transmit Identifier(1-4) TXID = 2 ?
Set the RXID of the local relay to match the TXID of the remote relay. For
example, in the three-terminal case, where Relay X transmits to Relay Y,
Relay Y transmits to Relay Z, and Relay Z transmits to Relay X:
Mirrored Bits Receive Default State(string of 1s, 0s or Xs)
87654321
RXDFLT=XXXXXXXX
?
Use the RXDFLT setting to determine the default state the M
IRRORED
B
ITS
should use in place of received data if an error condition is detected. The
setting is a mask of 1s, 0s, and/or Xs, for RMB1A–RMB8A, where X
represents the most recently received valid value.
Mirrored Bits RMB_ Pickup Debounce msgs(1-8) RMB1PU= 1 ?
Mirrored Bits RMB_ Dropout Debounce msgs(1-8) RMB1DO= 1 ?
Mirrored Bits RMB_ Pickup Debounce msgs(1-8) RMB2PU= 1 ?
Mirrored Bits RMB_ Dropout Debounce msgs(1-8) RMB2DO= 1 ?
Mirrored Bits RMB_ Pickup Debounce msgs(1-8) RMB3PU= 1 ?
Mirrored Bits RMB_ Dropout Debounce msgs(1-8) RMB3DO= 1 ?
Mirrored Bits RMB_ Pickup Debounce msgs(1-8) RMB4PU= 1 ?
Mirrored Bits RMB_ Dropout Debounce msgs(1-8) RMB4DO= 1 ?
Mirrored Bits RMB_ Pickup Debounce msgs(1-8) RMB5PU= 1 ?
Mirrored Bits RMB_ Dropout Debounce msgs(1-8) RMB5DO= 1 ?
Mirrored Bits RMB_ Pickup Debounce msgs(1-8) RMB6PU= 1 ?
Mirrored Bits RMB_ Dropout Debounce msgs(1-8) RMB6DO= 1 ?
Mirrored Bits RMB_ Pickup Debounce msgs(1-8) RMB7PU= 1 ?
Mirrored Bits RMB_ Dropout Debounce msgs(1-8) RMB7DO= 1 ?
Mirrored Bits RMB_ Pickup Debounce msgs(1-8) RMB8PU= 1 ?
Mirrored Bits RMB_ Dropout Debounce msgs(1-8) RMB8DO= 1 ?
Supervise the transfer of received data (or default data) to RMB1A–RMB8A
with the M
IRRORED
B
ITS
pickup and dropout security counters. Set the pickup
and dropout counters individually for each bit.
TXID
RXID
Relay X
1
3
Relay Y
2
1
Relay Z
3
2
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...