8.28
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Breaker Monitor, Metering, and Load Profile Functions
Demand Metering
The relay stores peak demand values to nonvolatile storage once per day (it
overwrites the previous stored value if it is exceeded). Should the relay lose
control power, it will restore the peak demand values saved by the relay at
23:50 hours on the previous day.
Demand metering peak recording is momentarily suspended when SEL
OGIC
control equation setting FAULT is asserted (= logical 1). See the explanation
for the FAULT setting in