Date _______________
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
SET.33
of 34
PORT Settings
(Serial Port Command SET P and Front Panel)
Protocol Settings (See Below)
Protocol (SEL, LMD, DNP, DNPE, MBA, MBB, MB8A,
MB8B)
PROTO
=
Protocol Settings
Set PROTO = SEL for standard SEL ASCII protocol. For SEL Distributed Port Switch
Protocol (LMD), set PROTO = LMD. Refer to
for details on the LMD protocol. For
Distributed Network Protocol (DNP), set PROTO = DNP or DNPE. Refer to
for details on
DNP protocol. For M
IRRORED
B
ITS
, set PROTO = MBA, MBB, MB8A, or MB8B. Refer to
for
details on M
IRRORED
B
ITS
.
The following settings are used if PROTO = LMD.
LMD Prefix (@, #, $, %, &)
PREFIX
=
LMD Address (01–99)
ADDR
=
LMD Settling Time (0–30 seconds)
SETTLE
=
Communications Settings
Baud Rate (300, 1200, 2400, 4800, 9600, 19200, 38400)
(38400 is not available on
PORT 1
)
SPEED
=
Data Bits (6, 7, 8)
BITS
=
Parity (O, E, N) {Odd, Even, None}
PARITY
=
Stop Bits (1, 2)
STOP
=
Other Port Settings (See Below)
Time-out (0–30 minutes)
T_OUT
=
Send Auto Messages to Port (Y, N, DTA)
AUTO
=
Enable Hardware Handshaking (Y, N, MBT)
RTSCTS
=
Fast Operate Enable (Y, N)
FASTOP
=
Other Port Settings
Set T_OUT to the number of minutes of serial port inactivity for an automatic log
out. Set T_OUT = 0 for no port time out.
Set AUTO = Y to allow automatic messages at the serial port. Set AUTO = DTA to use the serial port
with an SEL-DTA2 Display/Transducer Adapter.
Set RTSCTS = Y to enable hardware handshaking. With RTSCTS = Y, the relay will not send
characters until the CTS input is asserted. Also, if the relay is unable to receive characters, it
deasserts the RTS line. Setting RTSCTS is not applicable to serial
PORT 1
(EIA-485) or a port
configured for SEL Distributed Port Switch Protocol (LMD).
Set RTSCTS = MBT is only available at 9600 baud (SPEED selection). In this mode, the relay
deasserts the RTS line and does not monitor the CTS line. This selection is normally used with
M
IRRORED
B
ITS
, PROTO = MBA or MBB. See
for more detail.
Set FASTOP = Y to enable binary Fast Operate messages at the serial port. Set FASTOP = N to block
binary Fast Operate messages. Refer to
for the description of the SEL-351 Relay Fast
Operate commands.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...