2.10
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Installation
Making Rear-Panel Connections
Models 0351x0 and 0351x1 (Screw-Terminal Blocks)
Tools: Phillips or slotted-tip screwdriver
Parts: All screws are size #6-32. Locking screws can be requested from the
factory.
Chassis Ground
Model 0351xY
Ground the relay chassis at terminal
Z27
with the spade connector provided in
the previously discussed wiring harness (tab size 0.250 inches x 0.032 inches).
If the tab on the chassis is removed, the chassis ground connection can be
made with the size #6-32 screw.
Models 0351x0 and 0351x1
Ground the relay chassis at terminal
Z27
.
Power Supply
Model 0351xY
The power supply wiring harness includes a two-position connector and
factory-installed wire. Note the polarity indicators on terminals
Z25(+)
and
Z26(–)
. Control power passes through these terminals to a fuse and to the
switching power supply. The control power circuitry is isolated from the relay
chassis ground.
Plug the power supply connector into terminals
Z25
and
Z26
. The connector
locks in place upon insertion.
Section 1: Introduction and Specifications
for power supply ratings.
The relay power supply rating is listed on the serial number sticker on the
relay rear panel.
Models 0351x0 and 0351x1
Connect control voltage to the
POWER
terminals. Note the polarity indicators
on terminals
Z25(+)
and
Z26(–)
. Control power passes through these terminals
to a fuse and to the switching power supply. The control power circuitry is
isolated from the relay chassis ground.
Section 1: Introduction and Specifications
for power supply ratings.
The relay power supply rating is listed on the serial number sticker on the
relay rear panel.
Output Contacts
Model 0351x0
Model 0351
x
0 can be ordered with standard output contacts only. Refer to the
Specifications subsection
for output contact ratings.
Standard output contacts are not polarity dependent.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...