B.12
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Firmware Upgrade Instructions
Relay Firmware Upgrade Instructions
c. In the
Protocol
text box, select
1K Xmodem
if this
protocol is available.
If the computer does not have
1K Xmodem
, select
Xmodem
.
d. Click
Send
to send the file containing the new
firmware.
You should see a dialog box similar to
Incrementing numbers in the
Packet
box and a bar
advancing from left to right in the
File
box indicate that
a transfer is in progress.
Receiving software takes 10–15 minutes at 38400 bps,
depending on the relay. If you see no indication of a transfer in
progress within a few minutes after clicking
Send
, use the
REC
command again and reattempt the transfer.
After the transfer completes, the relay displays the following:
Upload completed successfully. Attempting a restart.
A successful restart sequence can take as long as two minutes,
after which time the relay leaves SEL
BOOT
. You will see no
display on your PC to indicate a successful restart.
Figure B.14
Selecting New Firmware to Send to the Relay
Figure B.15
Transferring New Firmware to the Relay
Step 6. Press
<Enter>
and confirm that the Access Level 0
=
prompt
appears on the computer screen.
Step 7. If you see the Access Level 0
=
NOTE:
Unsuccessful uploads can
result from Xmodem time-out, a
power failure, loss of communication
between the relay and the computer,
or voluntary cancellation. Check
connections, reestablish
communication, and start again at
.
If you want to reload the previous
firmware, begin at
and use the firmware you saved in
Download Existing Firmware on
page B.10
. Contact the factory for
assistance in achieving a successful
firmware upgrade.
NOTE:
The relay restarts in SEL
BOOT
if relay power fails while receiving
new firmware. Upon power-up, the
relay serial port will be at the default
2400 baud. Perform the steps
beginning in
to increase
the serial connection data speed.
Then resume the firmware upgrade
process at
.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...