A.2
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Firmware and Manual Versions
Firmware
This firmware differs from the previous versions as follows:
SEL-351-x-R316-V0-Z007005-D20060727
➤
Corrected negative-sequence directional element operation for
delta systems when Z1ANG is set low.
➤
Improved fault targeting for ungrounded systems.
➤
Added Z0MTA setting to allow use of Best Choice Ground
Directional Element™ logic on earthed systems with loads con-
nected phase-to-phase.
➤
Lowered single-phase power element minimum pickup to
.33 VA. (SEL-351-7 only).
➤
Fixed possible station dc battery monitor malfunction after a
settings or group change.
20060727
This firmware differs from the previous versions as follows:
SEL-351-x-R314-V0-Z006005-D20041210
➤
Manual update only. See
for a description of updates.
20050518
This firmware differs from the previous versions as follows:
SEL-351-x-R314-V0-Z006005-D20041210
➤
Added E79 setting options for enhanced recloser supervision
applications.
20041210
➤
Allowed phase and negative-sequence time overcurrent element
pickups to be set more sensitively.
➤
Allowed three-phase power element pickups to be set more sen-
sitively.
➤
Improved accuracy specification of voltage elements.
➤
Improved password security.
➤
Removed * (indication of where maximum current is) from raw
event report.
➤
Allowed Z1ANG and Z0ANG settings to be set as low as
5 degrees.
➤
Power Factor values found in DNP and ASCII communication
now match in resolution when polled simultaneously.
➤
Improved the timing of the setting group Relay Word Bit SG
n
to
update after a settings group change instead of during.
➤
DNP event report now uses peak values instead of cosine-fil-
tered values when an event is triggered by the Adaptive Over-
current Element.
➤
Improved the voltage scaling in the loss-of-potential (LOP)
logic.
➤
DNPE was improved to automatically refresh all stored values
upon any DNPE settings change.
➤
Improved initialization of communication ports when changing
protocols.
➤
Setting PSTDLY in DNP setting to 0 time delay was improved
to end communications faster.
This firmware applies to the manual date code listed:
SEL-351-x-R313-V0-Z005005-D20030908
➤
CT Saturation Protection was enhanced to improve security
with low-set instantaneous values.
➤
Corrected rounding error in breaker wear monitor.
20030908
This firmware applies to the manual date code listed:
SEL-351-x-R312-V0-Z005005-D20030714
➤
Optimized calibration settings for Petersen Coil units to
improve the factory calibration process.
20030714
Table A.1
Firmware Revision History
(Sheet 2 of 6)
Firmware Part/Revision No.
Description of Firmware
Manual Date
Code
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...