10.6
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Serial Port Communications and Commands
Communications Protocol
Communications Protocol
Hardware Protocol
All EIA-232 serial ports support RTS/CTS hardware handshaking. RTS/CTS
handshaking is not supported on the EIA-485
SERIAL PORT 1
.
To enable hardware handshaking, use the
SET P
command (or front-panel
{SET}
pushbutton) to set RTSCTS = Y. Disable hardware handshaking by
setting RTSCTS = N.
If RTSCTS = N, the relay permanently asserts the RTS line.
If RTSCTS = Y, the relay deasserts RTS when it is unable to receive
characters.
If RTSCTS = Y, the relay does not send characters until the CTS input is
asserted.
Software Protocols
The SEL-351 provides standard SEL protocols: SEL ASCII, SEL Distributed
Port Switch Protocol (LMD), SEL Fast Meter, and SEL Compressed ASCII.
In addition, the relay provides M
IRRORED
B
ITS®
and Distributed Network
Protocol (DNP3) as ordering options. The relay activates protocols on a per-
port basis. The SEL-351 is compatible with the SEL-DTA2 Display
Transducer Adapter. See
PORT Settings (Serial Port Command SET P and
To select SEL ASCII protocol, set the port PROTO setting to SEL. To select
SEL Distributed Port Switch Protocol (LMD), set PROTO = LMD. To select
DNP protocol, set PROTO = DNP.
SEL Fast Meter and SEL Compressed ASCII commands are active when
PROTO is set to either SEL or LMD. The commands are not active when
PROTO is set to DNP or M
IRRORED
B
ITS
.
SEL ASCII Protocol
SEL ASCII protocol is designed for manual and automatic communications.
1. All commands received by the relay must be of the form:
<command><CR> or <command><CRLF>
A command transmitted to the relay should consist of the
command followed by either a CR (carriage return) or a CRLF
(carriage return and line feed). You may truncate commands to
the first three characters. For example,
EVENT 1 <Enter>
would become
EVE 1 <Enter>
. Upper- and lowercase
characters may be used without distinction, except in
passwords.
NOTE:
The Enter key on most
keyboards is configured to send the
ASCII character 13 (^M) for a carriage
return. This manual instructs you to
press the Enter key after commands,
which should send the proper ASCII
code to the relay.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...