4.5
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Loss-of-Potential, Load Encroachment, and Directional Element Logic
Load-Encroachment Logic
Note that a positive-sequence impedance calculation (Z
1
) is made in the load-
encroachment logic in
. Load is largely a balanced condition; so
apparent positive-sequence impedance is a good load measure. The load-
encroachment logic only operates if the positive-sequence current (I
1
) is
greater than the Positive-Sequence Threshold defined in
. For a
balanced load condition, I
1
= phase current magnitude.
Forward load (load flowing out) lies within the hatched region labeled
ZLOUT. Relay Word bit ZLOUT asserts to logical 1 when the load lies within
this hatched region.
Reverse load (load flowing in) lies within the hatched region labeled ZLIN.
Relay Word bit ZLIN asserts to logical 1 when the load lies within this
hatched region.
Relay Word bit ZLOAD is the OR-combination of ZLOUT and ZLIN:
ZLOAD =
ZLOUT + ZLIN
Settings Ranges
.
Load-Encroachment
Setting Example
Example system conditions:
The PTs are connected line-to-neutral.
Setting
Description and Range
ZLF
Forward Minimum Load Impedance—corresponding to
maximum load flowing out
ZLR
Reverse Minimum Load Impedance—corresponding to
maximum load flowing in
0.05–64.00
Ω
secondary (5 A nominal phase
current inputs,
IA
,
IB
,
IC
) {150 V voltage inputs}
0.10–128.00
Ω
secondary (5 A nominal phase
current inputs,
IA
,
IB
,
IC
) {300 V voltage inputs}
0.25–320.00
Ω
secondary (1 A nominal phase
current inputs,
IA
,
IB
,
IC
) {150 V voltage inputs}
0.50–640.00
Ω
secondary (1 A nominal phase
current inputs,
IA
,
IB
,
IC
) {300 V voltage inputs}
PLAF
Maximum Positive Load Angle Forward (–90° to +90°)
NLAF
Maximum Negative Load Angle Forward (–90° to +90°)
PLAR
Maximum Positive Load Angle Reverse (+90° to +270°)
NLAR
Maximum Negative Load Angle Reverse (+90° to +270°)
Nominal Line-Line Voltage:
230 kV
Maximum Forward Load:
800 MVA
Maximum Reverse Load:
500 MVA
Power Factor (Forward Load):
0.90 lag to 0.95 lead
Power Factor (Reverse Load):
0.80 lag to 0.95 lead
CT ratio:
2000/5 = 400
PT ratio:
134000/67 = 2000
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...