10.17
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Serial Port Communications and Commands
Command Explanations
DAT Command (View/Change Date)
DAT
displays the date stored by the internal calendar/clock. If the date format
setting DATE_F is set to MDY, the date is displayed as month/day/year. If the
date format setting DATE_F is set to YMD, the date is displayed as year/
month/day.
To set the date, type
DATE mm/dd/yy <Enter>
if the DATE_F setting is
MDY. If the DATE_F is set to YMD, enter
DATE yy/mm/dd <Enter>
. To set
the date to June 1, 2001, enter:
=>
DATE 6/1/01 <Enter>
6/1/01
=>
You can separate the month, day, and year parameters with spaces, commas,
slashes, colons, and semicolons.
EVE Command (Event Reports)
Use the
EVE
command to view event reports. See
Reports, Sag/Swell/Interruption Report, and SER
for further details on
retrieving event reports.
GRO Command (Display Active Setting Group Number)
Use the
GRO
command to display the active settings group number. See
n Command (Change Active Setting Group) on page 10.36
for further details on settings groups.
HIS Command (Event Summaries/History)
HIS
x
displays event summaries or allows you to clear event summaries (and
corresponding event reports) from nonvolatile memory.
If no parameters are specified with the
HIS
command:
=
HIS <Enter>
the relay displays the most recent event summaries in reverse chronological
order.
If
x
is a number (1–23):
=
HIS X <Enter>
the relay displays the
x
most recent event summaries. The maximum number
of available event summaries is a function of the LER (length of event report)
setting.
If
x
is C or c, the relay clears the event summaries and all corresponding event
reports from nonvolatile memory.
The event summaries include the date and time the event was triggered, the
type of event, the fault location, the maximum phase current in the event, the
power system frequency, the number of the active setting group, the reclose
shot count, and the front-panel targets.
NOTE
: After setting the date, allow at
least 60 seconds before powering
down the relay or the new setting may
be lost.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...