USER’S MANUAL 
Rev. 03/2009 

 
 
 
 
00003

 

R

evo 

S

Solid-State Relay 

4x3,5A – 3x4,5A – 2x7A 

 

 

Summary of Contents for Revo Sx

Page 1: ...S r l Via Picasso 34 36 20025 Legnano MI ITALY Tel 39 0331 577479 Fax 39 0331 579479 E Mail info cdautomation com WEB www cdautomation com USER S MANUAL Rev 03 2009 00003 Revo Sx Solid State Relay 4x3 5A 3x4 5A 2x7A ...

Page 2: ... take away rings and other jewels from fingers and hands Authorized personnel working on thyristor unit under power supply voltage must work on insulated board Be secure that board is not connected to earth This listing does not represent a complete enumeration of all necessary safety cautions Protection protection The thyristor unit has a polymeric plastic cover to compliance to International spe...

Page 3: ...circuit by High speed fuses The Fuses must have I t 20 less than thyristor s I t The warranty of thyristor is null if no proper fuses are used Change the Fuses Press turn in counter clockwise and release Extract the fuse Caution High speed fuses are used only for the thyristor protection and can not be used to protect the installation Caution The warranty of thyristor is null if no proper fuses ar...

Page 4: ... in the same cabinet provide air circulation as represented Sometimes it is necessary to provide a fan to have better air circulation Dimensions and Fixing holes Weight 0 3Kg Environmental installation conditions Ambient temperature 0 40 C at nominal current Over 40 C use the Derating Curve Stocking temperature 25 C to 70 C Installation place Don t install at direct sun light where there are condu...

Page 5: ...CD Automation srl REVO 4x3 5A User s manual Diagram of control connection 4x3 5A Diagram of control connection 3x4 5A ...

Page 6: ...and other inductive loads must be equipped with opportune RC filter Use shielded bipolar cables for all the input and output signals The signal cables must not be near and parallel to the power cables Local regulations regarding electrical installation should be rigidly observed Use copper cables and wires rated for use at 75 C only Command cable dimensions suggested 0 5mm AWG 18 Power cable dimen...

Page 7: ... x 7A Voltage range 24 230V Repetitive peak reverse Voltage 230V 1200 Latching current 150mA eff Max peak one cycle 10ms 230A Leakage current 15mA eff I T Thyristor value tp 10msec 610 Frequency range 47 70Hz Power loss I Inom 4x4 2W Isolation Voltage 2500Vac Firing Type ZC firing mode is used with Logic Output from temperature controllers and the Thyristor operates like a contactor The Cycle time...

Page 8: ... signal Provide to give input signal Reverse the input signal polarity Green LED ON light on Load failure Load connection interruption Thyristor faulty Red LED FF is light off Check the load Check the wiring Substitute the faulty thyristor Thyristor unit doesn t go in conduction Red LED FF light on Fuse Fault Green LED ON is light on Substitute the faulty Fuse Load current flows also with no input...