6-28
Electrical Installation of Inverter
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
X2, W1 95 mm² terminal C and F (additional function)
RD51.1-xx-
Type
number
Execution
132
High current terminal
3
Terminal on mounting rail
160
High current terminal
3
Terminal on mounting rail
200
High current terminal
3
Terminal on mounting rail
Tab. 6-35:
Execution
Identification single connection
Identification
signification
C
F
Forced terminal for brake resistor
Tab. 6-36:
Identification single connection
RD51.1-xx-
Cable cross-section which can be connected
in mm²
AWG
132
35 - 95
2 – 4/0
160
35 - 95
2 – 4/0
200
35 - 95
2 – 4/0
Tab. 6-37:
Connection cross-section
15 – 20 Nm.
X80, starting lock-out
RD51.1-xx-
RD51.3-xx-
Type
Pole number
Execution
132
Plug-in connection
4
Plug on device
160
Plug-in connection
4
Plug on device
200
Plug-in connection
4
Plug on device
Tab. 6-38:
Execution
Identification single connection
Identification
signification
1
2
During operation, terminals 1 - 2 must be closed; when
they are opened, the start of the connected motor is
inhibited.
3
4
Starting lock-out floating acknowledge contact,
30 V DC / 1 A N / C contact
Tab. 6-39:
Identification single connection
RD51.1-xx-
RD51.3-xx-
Recommended
minimum cross-
section mm²
AWG
Cable cross-
section which can be
connected, mm²
AWG
132
1
18
0.08 – 1.5
28 - 16
160
1
18
0.08 – 1.5
28 - 16
200
1
18
0.08 – 1.5
28 - 16
Tab. 6-40:
Connection cross-section
0.22 – 0.25 Nm.
Execution
Connection cross-section
torque
Execution
Connection cross-section
torque
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......