![REXROTH RD 500 Series Applications Manual Download Page 107](http://html1.mh-extra.com/html/rexroth/rd-500-series/rd-500-series_applications-manual_1449588107.webp)
RD 500 RD51
Electrical Installation of Converter
4-19
DOK-RD500*RD51*******-IB04-EN-P
X2, Filter current feedback
RD51.1-x- Type
number
Execution
022
High current bushing terminal
3
Screw terminal
030
High current bushing terminal
3
Screw terminal
037
High current bushing terminal
3
Screw terminal
045
High current bushing terminal
3
Screw terminal
055
High current bushing terminal
3
Screw terminal
075
High current bushing terminal
3
Screw terminal
090
High current bushing terminal
3
Screw terminal
110
High current bushing terminal
3
Screw terminal
Tab. 4-38
Execution
Identification single connection
Identification signification
U6
V6
W6
Operation possible only with the original Bosch Rexroth filter
Tab. 4-39
Identification single connection
RD52.1-x- Cable cross-
section which can be connected,
mm²
AWG
Torque
in Nm
022
0.5 – 10
20 – 8
1.5 – 1.8
030
0.5 – 10
20 – 8
1.5 – 1.8
037
0.5 – 10
20 – 8
1.5 – 1.8
045
0.5 – 10
20 – 8
1.5 – 1.8
055
0.5 – 16
20 – 6
2.0 – 2.3
075
0.5 – 16
20 – 6
2.0 – 2.3
090
0.5 – 16
20 – 6
2.0 – 2.3
110
0.5 – 16
20 – 6
2.0 – 2.3
Tab. 4-40
Connection cross-section
See table.
Execution
Connection cross-section
Torque
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......