RD 500 RD51
Electrical Installation of Inverter
6-7
DOK-RD500*RD51*******-IB04-EN-P
Fuses Motor Inverter SFT Size Classes A and B
RD51.3-xx-
Maximum series fuse, type gL, A 1)
003
16
007
25
018
50
1):
or AC-fuses with min. 750 V at L / R = 20 ms.
Tab. 6-8
Series fuse
X2, Motor connection
RD51.2-xx-
RD51.3-xx-
Type
pole number
Execution
003
plug-in connection 3
Plug on device
005
plug-in connection 3
Plug on device
007
plug-in connection 3
Plug on device
015
plug-in connection 3
Plug on device
018
plug-in connection 3
Plug on device
Tab. 6-9
Execution
Identification single connection
Identification signification
U2
Motor connection U
V2
Motor connection V
W2
Motor connection W
Tab. 6-10
Identification single connection
Motor and shield connection for motor feeder cables
•
Cross section (PE) min. 10 mm² (AWG6)
•
steel plate lug on the housing with captive nut M5 (torque 2.5 –
3.0 Nm)
RD51.2-xx-
RD51.3-xx-
Cable cross-
section which can be connected 1), mm²
AWG
003
0.5 - 6
20 - 10
005
0.5 - 6
20 - 10
007
0.5 - 6
20 - 10
015
0.5 - 6
20 - 10
018
0.5 - 6
20 - 10
1):
As a result of the terminal size
Tab. 6-11
Connection cross-section
1.2 – 1.5 Nm
Fuses
Execution
Protective conductor connection
Connection cross-section
Torque
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......