3-30
Converter Technical Data
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
DG0006F1.FH7
Ambient temperature in °C
0,7
1
40
45
50
55
5
Degree of utilization at higher
ambient temperatures
Load f
actor
Fig. 3-30:
Utilization at a higher ambient temperature
Setup Elevations Exceeding 1000 Meters above Sea Level:
The utilization of the drive converter must be reduced (derated) according
to the diagram below for installation altitudes above 1000 meters above
sea level.
83%
80%
90%
100%
500
70%
0
1000
1500
2000
2500
Utilization
Insallation altitude in m above sea level
DGZU0008EN00.FH9
Fig.: 3-31 Derating depending on setup elevation
3.12 Assembly of Converter Size Classes A to E
•
The RD 500 units, sizes A to E are modular and are designed for
mounting in cabinets.
•
The units have a 22.5 mm mechanical grid pattern. Several drive units
can be mounted next to one another without any intermediate space
(with the exception of converter size classes A - B with cooling type P)
when using mounting rails with tapped holes (also refer to the
assembly example).
•
Assembly must be carried out perpendicular to a level construction
area.
•
A minimum clearance of 100 mm above and below the unit must be
maintained to ensure that the cooling air can flow unrestricted.
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......