10-2
Basic Functions
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
If the line supply is not connected and the “Standby” additional function is
selected, the “Starting lock out” warning message is not displayed.
Furthermore, the starting lock out cannot be used (alone) in the following
cases:
•
To electrically isolate the motor from the drive module power supply,
for example when replacing a motor
•
For other service, maintenance and cleaning work on the machine
•
For drive converters which have additional inverter modules
connected to the DC link (power terminal X1.C and X1.D).
Sequence and Procedure when Using the Starting lock
out
•
Withdraw the operating enablement (the drive should decelerate
along a ramp or coast down)
•
Wait until the drive signals “Ready” and it has come to a standstill
•
Activate the starting lock out
•
Check whether the starting lock out is active (warning, starting lock
out)
•
Issue the permission to carry out work on the drive
After the work has been completed
•
Deactivate the starting lock-out
•
“Ready” signal, wait a minimum of 2s
•
Issue the operating enablement