Electrical Installation of Converter
4-9
DOK-RD500*RD51*******-IB04-EN-P
X80 Starting lock-out (only in A1 and A2)
RD51.2-x-
Type
pole number
Execution
003
plug-in connection
4
Plug on device
005
plug-in connection
4
Plug on device
007
plug-in connection
4
Plug on device
015
plug-in connection
4
Plug on device
018
plug-in connection
4
Plug on device
Tab. 4-14
Execution
Identification single connection
Identification signification
1
2
During operation, terminals 1 - 2 must be closed; when they are
opened, the start of the connected motor is inhibited.
3
4
Starting lock-out floating acknowledge contact,
30 V DC / 1 A N / C contact
Tab. 4-15
Identification single connection
RD51.2-x- Recommended
minimum cross-section
mm²
AWG
Cable cross-
section which can be
connected, mm²
AWG
003
1
18
0.08 – 1.5
28 - 16
005
1
18
0.08 – 1.5
28 - 16
007
1
18
0.08 – 1.5
28 - 16
015
1
18
0.08 – 1.5
28 - 16
018
1
18
0.08 – 1.5
28 - 16
Tab. 4-16
Connection cross-section
0.22 – 0.25 Nm
Execution
Connection cross-section
Torque