RD 500 RD51
Electrical Installation of Inverter
6-9
DOK-RD500*RD51*******-IB04-EN-P
X83, 24 V Stand-by power supply for the electronics
(only in A1 and A2)
RD51.2-xx-
RD51.3-xx-
Type
pole number
Execution
003
plug
2
Plug on device
005
plug
2
Plug on device
007
plug
2
Plug on device
015
plug
2
Plug on device
018
plug
2
Plug on device
Tab. 6-15
Execution
Identification single connection
Identification signification
1
P24 V 24 V DC –15 / +20 %, ripple, max 5 % (VDE0411 / 500),
power consumption ~40 W, startup current 5 A
2
ground
Tab. 6-16
Identification single connection
RD51.2-xx-
RD51.3-xx-
Recommended
minimum cross-
section mm²
AWG
Cable cross-
section which can
be connected, mm²
AWG
003
1.5
16
0.2 – 2.5
24 - 14
005
1.5
16
0.2 – 2.5
24 - 14
007
1.5
16
0.2 – 2.5
24 - 14
015
1.5
16
0.2 – 2.5
24 - 14
018
1.5
16
0.2 – 2.5
24 - 14
Tab. 6-17
Connection cross-section
0.22 – 0.25 Nm
Execution
Connection cross-section
Torque