RD 500 RD51
Optional Device Functions
11-1
DOK-RD500*RD51*******-IB04-EN-P
11
Optional Device Functions
11.1 Additional function 24 V Stand-by Power Supply
General
The additional function standby allows the control electronics to operate
without any line supply voltage connected to the converter. A 24 V DC
control power supply voltage is required.
This additional function offers the following advantages:
•
Data sets can be parameterized, read and written into although the
converter is not connected to the line supply voltage
•
Data sets can be parameterized, read and written into although no DC
link voltage is connected to the inverter
•
Continued operation of field buses with the power supply disconnected
WARNING
Damage due to overload of the component!
⇒
To prevent ground loops, we recommend that the
24 V Standby power supply voltage be applied to
X83 in a floating manner.
WARNING
Damage due to overload of the component!
⇒
If the floating method is not used, X83 is not
protected from reverse polarity.
•
This applies to additional function V1 for size classes C - E
•
This applies to additional function V1 for size classes G - H
•
This applies to additional function A1 / A2 for size classes A - B
Technical Data
Necessary control power supply voltage on connector
X83
DC 24 V -15 / +20 %, ripple, max 5 % (VDE0411 / 500).
Size class
A – E
G
H
power
consumption W
40
80
160
startup current A
5
15
30
Tab.: 11-1
power consumption
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......