RD 500 RD51
Parameter Value Assignment
8-11
DOK-RD500*RD51*******-IB04-EN-P
Para-
meter
No.:
Name
Description / explanation
selectable options
Factory
setting
min ... max
values
Pass-
word
52 = IT no alarm. ext. (IT = input which is only active in
the “TEST” mode)
53 = IT no fault ext.
54 = IT fault reset
55 = IT fmin select
56 = IT direct. rotat.
57 = IT no volt. disc.
58 = IT no fast stop
59 = IT RFG park
60 = IT RFG-up stop
61 = IT motp. faster
62 = IT motp. slower
:
70 = O no function
71 = O ready to switch-on (O = output)
72 = O status: Ready to switch-on
73 = O ready
74 = O status: Ready
75 = O operation (run)
76 = O no fault
77 = O power-on inhibit
78 = O no alarm
79 = O motor rotating 1 (on & ((t <x.x sec) or (i>x.xx %)))
80 = O motor rotating 2 (on & (fact > fmin) & (i> x.xx %))
81 = O direction of rotation, clockwise
82 = O current limiting
83 = O not mot. alarm temp. (alarm: Motor temperature)
84 = O not motovertemp (fault: Motor temperature)
85 = O RFG up
86 = O RFG down
87 = O RFG reached
88 = O setpoint reached
89 = O setpoint in tolerance
90 = O fmin limiting
91 = O fmax limiting
92 = O TEST selected
93 = O control line contactor
94 = O f act
≤
f min
:
97 = O open mechanical brake
98 = O standstillsign.
0876
Dig. in- output2
I no function
1
As parameter 0875
0 ... 98
0877
Dig. in- output3
I no function
1
As parameter 0875
0 ... 98
0878
Dig. Input4
I test /
standard
1
As parameter 0875 from value 0 to 69
0 ... 69
0879
Dig. Input5
I fault reset
1
As parameter 0875 from value 0 to 69
0 ... 69
0880
Dig. Input8
I direct. rotat.
1
As parameter 0875 from value 0 to 69
0 ... 69
0881
Function relay
I no alarm
1
As parameter 0875 from value 70 to 93
70 ... 98
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......