Electrical Installation of Converter
4-51
DOK-RD500*RD51*******-IB04-EN-P
Converter
X12
TxD+ / RxD+
TxD- / RxD-
1
2
Open-loop Control
TxD+ / RxD+
TxD- / RxD-
Screen connection
to the next
Slave
AP520010EN00.FH9
Fig.: 4-22
Connection, standard interface
When using this interface, it should be ensured that the same interface
configuration is set for each bus node.
"SS1 slave address"; in this case, each bus node (station) has its own
address.
Bus Termination
The bus must be terminated at the first and last node of a bus system to
protect it against interference effects. The bus terminator is switched on
using a switch on the control card (refer to Fig.: 4-21
Terminal
diagram SR 17000).
Exception: