4-26
Electrical Installation of Converter
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
X1, 121 per 124
RD51.1-x- Type
Pole
number
Execution
132
Terminal strip
4
Slip-on terminal
160
Terminal strip
4
Slip-on terminal
200
Terminal strip
4
Slip-on terminal
315
Terminal strip
4
Slip-on terminal
400
Terminal strip
4
Slip-on terminal
Tab. 4-51
Execution
Identification single connection
Identification signification
121
122
Feedback signal contact (NC contact) from main contactor
123
124
Feedback signal contact (NC contact) from pre-charging
contactor
Tab. 4-52
Identification single connection
•
terminal rail with cable clamp size class G (stud M8 torque 12.0 Nm)
•
with M16 and M12 screws size class H (torque 120.0 Nm , 50 Nm)
RD51.1-x-
Cable cross-
section which can be connected 1), mm²
AWG
132
0.5 - 6
20 - 10
160
0.5 - 6
20 - 10
200
0.5 - 6
20 - 10
315
0.5 - 6
20 - 10
400
0.5 - 6
20 - 10
1):
As a result of the terminal size
Tab. 4-53
Connection cross-section
0.5 – 1.0 Nm.
Execution
Protective conductor connection
Connection cross-section
Torque
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......