4-28
Electrical Installation of Converter
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
X2, DC link Size class G
RD51.1-x-
number
Execution
132
feed-through terminal
3
terminal block
160
feed-through terminal
3
terminal block
200
feed-through terminal
3
terminal block
Tab. 4-55
Execution
Identification single connection
Identification signification
C
DC link terminal L+
D
DC link terminal L -
F
Internal brake resistor connected in the heat exchanger
between C and F
Tab. 4-56
Identification single connection
•
terminal rail with cable clamp (stud M8 torque 12.0 Nm)
RD51.1-x-
Cable cross-
section which can be connected 1), mm²
AWG
132
10 – 35
8 - 12
160
10 – 35
8 - 12
200
10 – 35
8 - 12
1):
As a result of the terminal size
Tab. 4-57
Connection cross-section
4.0 – 6.0 Nm.
RD51.1-x-
Cable cross-
section which can be connected
mm²
AWG
Torque
315
Per 4 x 35 - 95
2 – 4/0
15.0 – 20.0
400
Per 4 x 35 - 95
2 – 4/0
15.0 – 20.0
Tab. 4-58
Connection cross-section
Execution
Protective conductor connection
Connection cross-section
Torque
Connection cross-sectionas use
as additional function Z1 and W1