Mounting Drawing for Devices with External Heat Exchanger for Wall
Mounting
340
Connection
Cooling circuit
for M8
cooling air
Hot discharged air
for PE-Connection
if required
Cable length max. 5 m
200
MB520028EN01.FH9
Dimension in mm
Hose length max. 5 m
Coupling with self closing values are contain
Fig.: 3-53
Dimension sheet for wall mounting, size class H
3.16 Working on the Coolant Circulation System Size Classes
G and H
Both versions of the liquid-cooled drive units, with integrated and external
heat exchanger, are supplied filled with liquid. The coolant comprises tap
water and antifreeze, type Antifrogen N (Clariant). It is mixed in the ratio 1
: 1. This guarantees frost protection down to -30 °C.
CAUTION
Antifreeze is hazardous to health!
⇒
If antifreeze is swallowed, immediately consult a
doctor and keep the packaging or label for reference.
CAUTION
Mixture with other antifreezes!
⇒
Do not mix the coolant with other antifreezes.
⇒
Only use the specified antifreeze if coolant must be
added to installed drive units.
WARNING
Burns due to hot components with
temperatures above 30 °C!
⇒
Wear protective gloves
⇒
Replace devices only when the liquid circulation
system has cooled
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......