6-14
Electrical Installation of Inverter
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
X1, SNT supply
RD51.1-xx-
RD51.3-xx-
Type
Num-
ber
Execution
022
Universal terminal
2
With mounting foot
030
Universal terminal
2
With mounting foot
037
Universal terminal
2
With mounting foot
045
Universal terminal
2
With mounting foot
055
Universal terminal
2
With mounting foot
075
Universal terminal
2
With mounting foot
090
High current bushing terminal
2
Screw connection
110
High current bushing terminal
2
Screw connection
Tab. 6-26
Execution
Identification single connection
Identification signification
C1
SNT
Bridge to connection C
D1
SNT supply -
Bridge to connection D
Installation must
be inherently
short-circuit-proof
Tab. 6-27
Identification single connection
RD51.1-xx-
RD51.3-xx-
Cable cross-
section which can be
connected, mm²
AWG
Torque
in Nm
022
0.2 – 4
24 – 12
0.6 – 0.8
030
0.2 – 4
24 – 12
0.6 – 0.8
037
0.2 – 4
24 – 12
0.6 – 0.8
045
0.2 – 4
24 – 12
0.6 – 0.8
055
0.2 – 4
24 – 12
0.6 – 0.8
075
0.2 – 4
24 – 12
0.6 – 0.8
090
0.5 – 10
20 – 8
2.0 – 2.3
110
0.5 – 10
20 – 8
2.0 – 2.3
Tab. 6-28
Connection cross-section
See table.
Execution
Connection cross-section
Torque
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......