RD 500 RD51
Inverter Technical Data
5-7
DOK-RD500*RD51*******-IB04-EN-P
5.7
Technical Data for Size Classes G with Pulse Frequency f
p
= 12 kHz
12 kHz
RD51.1
132
160
200
Supply voltage DC 530 ... 670 V (±10 %)
Output frequency
1)
Hz
0 - 1000
0 - 500
Rated current
A 140
170
210
Peak current for t = 60 s A 182
221
273
t = 1 s A 238
289
357
Rated output S
N
kVA 92
112
138
Peak power for t = 60 s kVA
120
145
180
Ambient conditions, noise suppression level, interference immunity
Environmental class
3K3 according to DIN IEC 721-3-3 (ambient temperature 0 – 40 °C
operation, to 50 °C power reduction at 2.5 % per K)
Cooling air requirement
m³ / s
0.4
0.4
0.6
Power loss kW
3.0
3.7
4.6
Radio int. sup. level / noise immunity
A 1 according to EN 55011 / EN 61800-3
Mechanical design
Size classes
G
G
G
Degree of protection
IP 20 according to EN 60529 (without connection terminals)
Weight of inverter for the various cooling types
F Forced air cooling with integrated
liquid circuit kg 128
128
128
R Liquid cooling with
internal pump kg 105
105
105
1):
If Output frequency >150 Hz the additional function M1 is required
(without integrate Motor filter)
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......