RD 500 RD51
Electrical Installation of Converter
4-49
DOK-RD500*RD51*******-IB04-EN-P
Parameterizing Service Interface RS232
The service interface also operates with the USS protocol.
However, the protocol type is fixed (4 / 6 words, even parity, 1 stop bit).
See function description: DOK-RD500-RD51*xxVRS*-FKxx-EN-P.
The baud rate can be selected using P0499.
Parameter
No.:
Name
Description / explanation
of selectable options
Factory setting
min / max values
Pass-
word
0499
RS232 baud rate X11
Parameter value:
0 = 1200 Baud
1 = 2400 Baud
2 = 4800 Baud
3 = 9600 Baud
4 = 19,200 Baud
5 = 38,400 Baud
6 = 57,600 Baud
7 = 76,800 Baud
9600 baud
0 - 7
2
Fig.:4-20
Parameters for RS232
The following settings should be observed:
Can be set using P0499: 1200, 2400, 4800, 9600 (factory setting), 19200,
38400, 57600, 76800 baud
8
Even
1
USS protocol, 4 / 6 words
Baud rate:
Data bits:
Parity:
Stop bits:
Protocol type: