7-4
Operator Control and Visualization
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
CAUTION
Damage caused by parameterizing errors!
⇒
The filter or motor could be damaged if the pulse
frequency (P0026) is incorrectly selected.
Fault Messages when Parameterizing
Error message
Cause
Solution
Parameter is not
accessible in the
basic parameterization.
Parameter numbers which are not
accessible have been entered into the
numerical list.
Only pre-defined parameters are available in the
basic parameterization. Only parameter numbers
from the Tables in Section 5 can be entered.
Please
select
basic parameterization
The selected parameter is a macro
parameter and is not accessible in the
free parameterization.
Change into the basic parameterization.
Caution! Data could be lost.
Parameter inhibited
Drive is operational.
Inhibit the inverter and then change the parameter.
Data conflict
(general)
Some parameter settings are dependent on others. If a parameter is changed and is
acknowledged with
Enter
, then data conflicts can occur.
Data conflict
e.g. P0182 with P0183
The V/Hz characteristics are not
correct. The frequencies must have a
minimum
1 Hz clearance between them.
Initially accept the value of the first parameter
change with
Prog
after the second parameter
change acknowledge with
Enter
to save.
Data conflict
e.g. P0870
steady-state<==>dynam
Changing the “steady-state” into the
“dynamic On / Off command” or vice
versa. Steady-state / dynamic On / Off
operation for the test / normal
operating modes cannot be selected,
mixed.
Initially accept the value of the first parameter
change with
Prog
, after the second parameter
change acknowledge with
Enter
to save.
Data conflict
e.g. P0875
with dynam. ON / OFF
In the device control is ON / OFF
(P0870 / 0871) “terminal static”
selected. The function “enable
operation” is permanently switched on
digital input 7
The function “enable operation” can only switched
on an optional digital input, when the command ON
/ OFF (P0870 / 0871) are setting dynamic.
1:
For parameters which are dependent on the motor data set
changeover (P0070), both data sets (indexes 0 and 1) are
monitored. This includes the parameter set which isn’t active.
Fig. 7-7: Fault messages when parameterizing
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......