RD 500 RD51
Parameter Value Assignment
8-17
DOK-RD500*RD51*******-IB04-EN-P
Para-
meter
No.:
Name
Description / explanation
selectable options
Factory setting
min ... max values
Pass-
word
0388
PTC evaluation
X15
Supplementary parameter for PTC in P0385
Fault
2
The following options can be selected when the
selected PTC switching value (P389) is reached:
0 = alarm (alarm, motor temperature)
1 = fault (fault, motor temperature)
0 / 1
0389
PTC switch value
X15
Supplementary parameter for PTC in P0385
4000 W
1
Enters the resistance switching threshold to initiate
the response set using P0388 (PTC evaluation).
1000 .. 4500 W
0565
Sel. overload prot.
No response
2
The overload protection function is implemented
corresponding to the SIEMENS 3UB1 overload relay,
setting Class 10.
The following options can be selected for the
response of the IxT overload protection function:
0 = no action 1 = alarm 2 = fault
0 ... 2
0566.00
Curr. overload prot.
Refer to Fig. 8-5: Emulation of the thermal
overload release.
0.5 A
1
Current threshold for the Ixt overload protection
function. When the Ixt threshold is reached, the
response, set using P565, is initiated.
Emulates the thermal overload response
When the motor rating plate data is changed, P0566
is set to the rated motor current.
0.5 ... 6553.5 A
1
0532.00
Fixv. current limit
100.00 %
1
Enters the current limit
100 % correspond to the contents of parameter
P0374 (factory setting: Continuous output current of
the drive).
0.00 ... 190.00 %
1
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......