![REXROTH RD 500 Series Applications Manual Download Page 40](http://html1.mh-extra.com/html/rexroth/rd-500-series/rd-500-series_applications-manual_1449588040.webp)
3-8
Converter Technical Data
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
3.8
Technical Data for Size Classes G and H with Pulse
Frequency f
p
= 4 kHz / 8kHz
4 kHz
8 kHz
RD51.1
132
160
200
315
400
132
160
200
315
400
Rated motor output
1)
kW 132
160
200
315
400
110
132
160
200
315
Supply voltage, 3-phase 380 ... 480 V AC (±10 %)
2)
Output frequency
4)
Hz
0 - 250
0 - 150
0 - 500
0 - 250
Rated current
A
230
290
350
540
680
195
230
280
400
540
Peak current for t = 60 s A
299
377
455
702
884
254
299
364
520
702
t = 1 s A
391
493
595
918
1156
332
391
476
680
918
Rated output S
N
kVA 151
191
230
355
448
128
151
184
263
355
Peak power for t = 60 s kVA
197
248
299
462
582
166
197
240
342
462
Supply voltage, 3-phase 500 V AC (±10 %)
Output frequency
4)
Hz
0 - 250
0 - 150
0 - 500
0 - 250
Rated current
A
190
240
280
432
550
160
190
240
345
432
Peak current for t = 60 s A
247
312
364
562
715
208
247
312
449
562
t = 1 s A
323
408
476
734
935
272
323
408
587
734
Rated output S
N
kVA 156
197
230
355
452
132
156
197
284
355
Peak power for t = 60 s kVA
203
257
299
462
588
171
203
257
369
462
Ambient conditions, noise suppression level, interference immunity
Environmental class
3K3 according to DIN IEC 721-3-3 (ambient temperature 0 – 40 °C operation, to
50 °C power reduction at 2.5 % per K)
Cooling air requirement
m³ / s
0.4
0.4
0.6
0.8
1.2
0.4
0.4
0.6
0.8
1.2
Power loss kW 5.2
6.5
7.7
11.8
15.0
4.4
5.2
6.5
9.5
11.8
Radio int. sup. level / noise immunity
A 1 according to EN 55011 / EN 61800-3
Mechanical design
Size classes
G
G
G
H
H
G
G
G
H
H
Degree of protection
IP 20 according to EN 60529 (without connection terminals)
Weight of converter for the various cooling types
F Forced air cooling with integrated
liquid circuit kg 180
180
180
358
358
180
180
180
358
358
R Liquid cooling with
internal pump kg
157
157
157
312
312
157
157
157
312
312
Performance data of chopper
Continuous power kW
40
40
40
2 x 40 2 x 40 40
40
40
2 x 40 2 x 40
Continuous power
3)
kW
100
100
100
2x100 2x100 100
100
100
2x100 2x100
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......