RD 500 RD51
Electrical Installation of Converter
4-7
DOK-RD500*RD51*******-IB04-EN-P
X2, Motor connection
RD51.2-x-
Type
pole number
Execution
003
plug-in connection 3
Plug on device
005
plug-in connection 3
Plug on device
007
plug-in connection 3
Plug on device
015
plug-in connection 3
Plug on device
018
plug-in connection 3
Plug on device
Tab. 4-8
Execution
Identification single connection
Identification signification
U2
Motor connection U
V2
Motor connection V
W2
Motor connection W
Tab. 4-9
Identification single connection
Motor and shield connection for motor feeder cables
Cross section (PE) min. 10 mm² (AWG 6)
steel plate lug on the housing with captive nut M5 (torque 2.5 – 3.0 Nm)
RD51.2-x-
Cable cross-
section which can be connected 1), mm²
AWG
003
0.5 - 6
20 - 10
005
0.5 - 6
20 - 10
007
0.5 - 6
20 - 10
015
0.5 - 6
20 - 10
018
0.5 - 6
20 - 10
1):
As a result of the terminal size
Tab. 4-10
Connection cross-section
1.2 – 1.5 Nm
Execution
Protective conductor connection
Connection cross-section
Torque