RD 500 RD51
Electrical Installation of Inverter
6-13
DOK-RD500*RD51*******-IB04-EN-P
Description of Inverter Power Terminals Size Classes C - E
X1 DC link connection
RD51.1-xx-
RD51.3-xx-
Type
number
Execution
022
High current terminal
2
Terminal on mounting rail
030
High current terminal
2
Terminal on mounting rail
037
High current terminal
2
Terminal on mounting rail
045
High current terminal
2
Terminal on mounting rail
055
High current terminal
2
Terminal on mounting rail
075
High current terminal
2
Terminal on mounting rail
090
High current terminal
2
Terminal on mounting rail
110
High current terminal
2
Terminal on mounting rail
Tab. 6-23
Execution
Identification single connection
Identification signification
C
DC link connection (IC) L+
D
DC link connection (IC) L-
Tab. 6-24
Identification single connection
•
Cross section (PE) min. 10 mm² (AWG 6)
•
steel plate lug on the housing with captive nut
•
... M6 at Size class C and D (torque 4.2 – 5.0 Nm)
•
... M8 at Size class E (torque 12 Nm)
RD51.1-xx-
RD51.3-xx-
Cable cross-
section which can be
connected 1), mm²
AWG
Torque
in Nm
022
25 – 50
3 – 1/0
6.0 – 8.0
030
25 – 50
3 – 1/0
6.0 – 8.0
037
25 – 50
3 – 1/0
6.0 – 8.0
045
25 – 50
3 – 1/0
6.0 – 8.0
055
35 – 95
2 – 4/0
15.0 – 20.0
075
35 – 95
2 – 4/0
15.0 – 20.0
090
50 – 150
1/0 – 300MCM
25.0 – 30.0
110
50 – 150
1/0 – 300MCM
25.0 – 30.0
1):
As a result of the terminal size
Tab. 6-25
Connection cross-section
See table.
Execution
Protective conductor connection
Connection cross-section
Torque
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......