RD 500 RD51
Parameter Value Assignment
8-25
DOK-RD500*RD51*******-IB04-EN-P
Para-
meter
No.:
Name
Description / explanation
selectable options
Factory setting
min ... max values
Pass-
word
0037.00
Display, lines 1,2,3
f actual
0
Selects the operating display for line 1.
0 = status (drive status message)
1 = actual speed (electrical)
2 = output effective current
3 = output current (actual apparent current)
4 = output voltage
5 = DC link voltage
6 = frequency actual value
7 = frequency setpoint
8 = P act (actual apparent power)
9 = P active (active power which the motor takes)
0 ... 9
0037.01
Display, lines 1, 2, 3
Frequency
setpoint
0
Selects the operating display for line 2.
As for parameter 0037.00.
0 ... 9
0037.02
Display, lines 1, 2, 3
Status
0
Selects the operating display for line 3.
As for parameter 0037.00.
0 ... 9
0734
Display contrast
11
0
Sets the contrast for the operator panel display
10 ... 20
0768
Illum. display
10 min
0
Background lighting in the operator panel display
0 = switched out
1 ... 998 = minutes remains switched-in after the
last key was pressed
999 = continually switched-in
0 ... 999
0026
Pulse frequency
4 kHz
2
Pulse frequency of the inverter drive
0072
Source parameter
All busses SSx
2
Specifies from which source parameters can be set.
0 = Keypad, PC (RS232),
1 = Bus SS1,
2 = Bus SS2,
3 = Bus SS4,
4 = All busses,
5 = Bus SS6
0 ... 5
0280
Ramp-up time
5.000 sec
1
Ramp-up time generator (RFG)
0.000 ...
900000.000
0281
Ramp-down time
5.000 sec
1
Ramp-down time generator (RFG)
0.000 ...
900000.000
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......