Chapter 4: Connecting External Equipment (Optional)
26
Combining Regular Asset Sensors
Each tag port on the regular asset sensor corresponds to a rack unit and
can be used to locate IT devices in a specific rack (or cabinet).
For each rack, you can attach asset sensors up to 64U long, consisting
of one MASTER and multiple SLAVE asset sensors.
The difference between the master and slave asset sensors is that the
master asset sensor has an RJ-45 connector while the slave does not.
The following diagram illustrates some asset sensors. Note that Raritan
provides more types of asset sensors than the diagram.
8U MASTER asset sensor with 8 tag ports
8U SLAVE asset sensor with 8 tag ports
5U "ending" SLAVE asset sensor with 5
tag ports
Note: Unlike general slave asset sensors, which have one DIN connector
respectively on either end, the ending slave asset sensor has one DIN
connector on only one end. An ending asset sensor is installed at the
end of the asset sensor assembly.
To assemble asset sensors:
1. Connect a MASTER asset sensor to an 8U SLAVE asset sensor.
Plug the white male DIN connector of the slave asset sensor into
the white female DIN connector of the master asset sensor.
Summary of Contents for EMX2-888
Page 19: ...Chapter 1 Introduction 5 Retrieval of the link local IPv4 address See IPv4 Address on page 72...
Page 71: ...Chapter 4 Connecting External Equipment Optional 57...
Page 148: ...Chapter 6 Using the Web Interface 134 LHX 20 SHX 30 LHX 40 PowerLogic PM710...
Page 526: ...Appendix H RADIUS Configuration Illustration 512 Note If your EMX uses PAP then select PAP...
Page 531: ...Appendix H RADIUS Configuration Illustration 517 14 The new attribute is added Click OK...
Page 532: ...Appendix H RADIUS Configuration Illustration 518 15 Click Next to continue...