Chapter 8: Using the Command Line Interface
415
config:#
sensor externalsensor <n> <sensor type> lowerWarning <option>
Set the deassertion hysteresis for an environmental sensor:
config:#
sensor externalsensor <n> <sensor type> hysteresis <hy_value>
Set the assertion timeout for an environmental sensor:
config:#
sensor externalsensor <n> <sensor type> assertionTimeout <as_value>
Variables:
<n> is the ID number of the environmental sensor that you want to
configure. The ID number is available in the EMX web interface or
using the command "
show externalsensors <n>
" in the CLI. It is
an integer between 1 and 32.
<sensor type> is one of these sensor types:
temperature,
absoluteHumidity, relativeHumidity, airPressure, airFlow
or
vibration
.
Note: If the specified sensor type does not match the type of the
specified environmental sensor, this error message appears:
"Specified sensor type 'XXX' does not match the sensor's type
(<sensortype>)," where XXX is the specified sensor type, and
<sensortype> is the correct sensor type.
<option> is one of the options:
enable
,
disable
or a numeric value.
Option
Description
enable
Enables the specified threshold for a specific
environmental sensor.
disable
Disables the specified threshold for a specific
environmental sensor.
A numeric
value
Sets a value for the specified threshold of a
specific environmental sensor and enables this
threshold at the same time.
<hy_value> is a numeric value that is assigned to the hysteresis for
the specified environmental sensor. See
"To De-assert" and
Deassertion Hysteresis
(on page 534).
<as_value> is a number in samples that is assigned to the assertion
timeout for the specified environmental sensor. It ranges between 1
and 100. See
"To Assert" and Assertion Timeout
(on page 532).
Summary of Contents for EMX2-888
Page 19: ...Chapter 1 Introduction 5 Retrieval of the link local IPv4 address See IPv4 Address on page 72...
Page 71: ...Chapter 4 Connecting External Equipment Optional 57...
Page 148: ...Chapter 6 Using the Web Interface 134 LHX 20 SHX 30 LHX 40 PowerLogic PM710...
Page 526: ...Appendix H RADIUS Configuration Illustration 512 Note If your EMX uses PAP then select PAP...
Page 531: ...Appendix H RADIUS Configuration Illustration 517 14 The new attribute is added Click OK...
Page 532: ...Appendix H RADIUS Configuration Illustration 518 15 Click Next to continue...