Chapter 5: Using the EMX
78
The two termination points to the right are associated with channel 1
(CC1 as indicated in the panel), and the two to the left are associated
with channel 2 (CC2).
With this design, there are two ways to plug discrete detectors/switches:
Connect the discrete detectors/switches while the terminal module is
attached to the EMX.
Connect the discrete detectors/switches while the terminal module is
separated from the EMX.
Important: It is not guaranteed that all third-party detectors/switches are
compatible with the EMX. You need to test the compatibility after
installing them.
To make connections when the terminal module is attached to
the EMX:
1. Strip the insulation around 12 mm from the end of each wire of
discrete detectors/switches.
2. Fully insert each wire of both detectors/switches into each
termination point.
Plug both wires of a detector/switch into the two termination
points to the left.
Plug both wires of the other detector/switch into the two
termination points to the right.