Chapter 4: Connecting External Equipment (Optional)
41
For the cabling length restrictions, see
Supported Maximum DPX
Sensor Distances
(on page 45).
Warning: For proper operation, wait for 15-30 seconds between each
connection operation or each disconnection operation of
environmental sensor packages.
To connect a DPX sensor package with a factory-installed
sensor cable:
Plug the sensor cable's RJ-12 connector into the RJ-12 SENSOR
port on the EMX.
To connect a DPX differential air pressure sensor:
1. Plug one end of a Raritan-provided phone cable into the IN port of a
differential air pressure sensor.
2. Plug the other end of this phone cable into the RJ-12 SENSOR port
on the EMX.
3. If intended, connect one DPX sensor package to the OUT port of the
differential air pressure sensor. It can be any DPX sensor package,
such as a DPX-T3H1.
The EMX device
Raritan differential air pressure sensors
One DPX sensor package (optional)