Chapter 6: Using the Web Interface
276
7. Click
OK.
Configuring Temperature and Fan Thresholds
An LHX/SHX heat exchanger is implemented with various sensors for
detecting the air temperature, water temperature, and fan speed.
You can set thresholds for these sensors so that the EMX alerts you
when any sensor readings are getting close to a critical condition.
The LHX/SHX settings are stored on the EMX port where the LHX/SHX
device is connected, and are lost if that device is moved to a different
port.
To configure the thresholds for a sensor:
1. Expand the Auxiliary Ports or Feature Ports folder as needed.
2. Click the desired LHX/SHX device. Its page opens in the right pane.
3. Select the desired sensor in the Sensors table and click Setup
Thresholds, or double-click that sensor.
The setup dialog for the selected sensor appears.