11-4 Troubleshooting
OMNUC G5-Series AC Servo Drives Users Manual (Built-in MECHATROLINK-II communications type)
11
Error and Maintenance
33
Interface I/O allocation
error
Occurs when the power
supply is turned ON.
• There is a duplicate
setting in the I/O signal
function allocation.
• Specify the undefined
number with the I/O
signal function allocation.
• Set the function
allocation correctly.
• The latch input function
is allocated incorrectly.
• Assign it to IN5, IN6
and IN7.
• Assign it in NO contact.
• Assignments in all
modes must be the
same.
34
Overrun limit error
Occurs during operation.
• The Overrun Limit
Setting (Pn514) was
exceeded during
operation.
• Adjust the gain.
• Increase the set value
of Pn514.
• Set Pn514 to 0 to
disable the function.
36
Parameter error
Occurs when the power
supply is turned ON.
• There are data errors
in the parameters that
were read.
• Reset all parameters.
• The drive is faulty.
• Replace the Servo Drive.
37
Parameters destruction Occurs when the power
supply is turned ON.
• The parameters that
were read are corrupt.
• Replace the Servo Drive.
Alarm
number
Error conditions
Status when error
occurs
Cause
Measures