Information (Output operation mode) assigned to auxiliary output
It is recommended that the Position 2 of the DIP Switch be set at OFF (DIP Switch Disabled).
Information Name
Description
(Auxiliary output is turned ON under the following condition)
Safety output information
When the safety outputs are in the ON state
Interlock information
Under the INTERLOCK state
Lockout information
Under the LOCKOUT state
Excess power-on time
information
When power-on time exceeds power-on time threshold
Excess load switching
frequency information
When load switching frequency exceeds load switching frequency threshold
Stable-state information
When light intensity, which is constantly monitored, is 170% or higher of ON-threshold
Muting information
Under the MUTING state
Override information
Under the OVERRIDE state
Muting/Override information
Under either the MUTING or OVERRIDE state
Light level diagnosis
information
When the F3SG-SR is unblocked and light intensity is within a range from 100% to 170% of
ON-threshold for 10 s or longer
Warning Zone Information
When warning zone is blocked
PSDI Information
When the F3SG-SR is ready to be blocked for feeding or removing parts
Blanking bream unblocked
information
When Fixed-Blanking or Floating Blanking beams are unblocked
Troubleshooting support
signal
When one of the signals of Sequence error information, Interference/vibration information and
Light level diagnosis information is in the ON state.
Designated beam output
information
When a designated beam is blocked or unblocked
Sequence error information
Under the MUTING SEQUENCE ERROR state or the INTERLOCK SEQUENCE ERROR
state
Reset-input information
When RESET/EDM/Override input is in the ON state
Mute A input information
When MUTE A input is in the ON state
Mute B input information
When MUTE B input is in the ON state
EDM input information
When EDM signal input is in the ON state
Individual cascaded sensor
output (Channel 1)
When the safety outputs of the primary sensor in cascade connection are in the ON state
Individual cascaded sensor
output (Channel 2)
When the safety outputs of the 1st secondary sensor in cascade connection are in the ON
state
Individual cascaded sensor
output (Channel 3)
When the safety outputs of the 2nd secondary sensor in cascade connection are in the ON
state
Blanking/Warning-zone
information
When Fixed Blanking, Floating Blanking, Reduced Resolution or Warning Zone function is
enabled
Instantaneous block
information
When the F3SG-SR system stops accidentally due to interference or vibration. (In case of
cascade connection, when any of cascaded segments comes under this condition.)
Pre-reset Information
Under Pre-reset state
Communication quality
diagnosis information
Assigned when retry occurs in communications due to noise or short-circuit of the
communication line.
Recoverable error information
Assigned when a recoverable error occurs.
Replacement-recommended
error information
Assigned when a replacement-recommended error occurs.
No assignment (function OFF) This function is disabled.
Summary of Contents for F3SG-SR Series
Page 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Page 18: ...xvi Introduction F3SG SR User s Manual...
Page 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Page 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Page 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Page 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...