Teach-in (Fix Blanking / Floating Blanking)
F3SG-SR
User’s Manual
Setting with Intelligent Tap
*2 If the setting value is not an allowable one, the setting is invalid. The following cases are judged as
invalid.
•All beams have been configured as a Fixed Blanking zone (including allowable beams).(Fig. 1)
•All beams except the beams at both ends have been configured as a Fixed Blanking zone. (Fig. 2)
•End beams (synchronization beams) have been configured as a Fixed Blanking zone at the same
time. (Primary sensor in Optical Synchronization only) (Fig. 3)
•The Teach-in must be performed with at least 1 beam being blocked.(Fig. 4)
•When the Teach-in is performed for more than one Fixed Blanking zones, there must be at least 3
beams between the blocking objects.(Fig. 5)
•Four or more areas have been configured as Fixed Blanking zones for one channel.
Indicator status of the F3SG-SR when Teach-in setting is valid or invalid
(6) Restart
<When operating the F3SG-SR with the Intelligent Tap not connected>
When completing the Teach-in setting, power off the F3SG-SR and remove the Intelligent Tap. Then
restart the F3SG-SR.
<When operating the F3SG-SR with the Intelligent Tap connected>
When completing the Teach-in setting, power off the F3SG-SR and set the DIP Switch Position 1 at
OFF (Unlock). Then restart the F3SG-SR.
There are two ways to restart.
• Power cycling
• Pressing and holding reset switch (for 1 s or longer): Set the DIP Switch Position 1 at OFF (Unlock).
(If restarting the F3SG-SR with the DIP Switch Position 1 set at ON (Lock), the configured zone will
be invalid. In this case, try the steps again from (4).)
After the restarting, the F3SG-SR waits for the Backup process of the settings. Perform the Backup
process. After the Backup process is complete, the power off the F3SG-SR and set the DIP Switch
Position 1 at ON (Lock). Check if the DIP Switch Positions 2 to 8 and other settings are configured as
intended, and then restart the F3SG-SR. After the F3SG-SR is restarted, the check if the Fixed
Blanking zone and other settings are properly configured.
Refer to 3-6-2. Performing Backup for more information on the Backup procedure.
Teach-in setting is valid
Teach-in setting is invalid
LED Indicator
Status
LED Indicator
Status
SEQ
SEQ
CFG
CFG
ABI
Area blocked by
blocking object is
illuminated in red
ABI
Area blocked by
blocking object is
illuminated in red
Upper
Upper
Lower
Lower
Fig. 1
Upper
Upper
Lower
Lower
Fig. 2
Upper
Upper
Lower
Lower
Fig. 3
Fig. 4
Upper
Upper
Lower
Lower
Upper
Upper
Lower
Lower
Fig. 5
OFF
Blinking
illuminated
Blinking
Summary of Contents for F3SG-SR Series
Page 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Page 18: ...xvi Introduction F3SG SR User s Manual...
Page 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Page 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Page 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Page 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...