95
F3SG-SR
User’s Manual
Chapter
2
Fixed Blanking
System Operation and Functions
E
2-15-3. Setting with Intelligent Tap
Fixed blanking can be configured using Positions 6 and 7 of the DIP Switch of the Intelligent Tap.
The Fixed Blanking Monitoring function is configured as Lockout.
Make sure the Position 2 of the DIP Switch is set at ON (DIP Switch Enabled) to activate the settings by the DIP Switch.
2-15-4. Setting with SD Manager 3
The user can make changes to the settings of this function by the SD Manager 3.
Setting is required for each sensor segment in case of a cascade connection.
It is recommended that the Position 2 of the DIP Switch be set at OFF (DIP Switch Disabled).
Setting the Fixed Blanking Monitoring function to Disable Monitoring may create an undetectable area where a person
can block the F3SG-SR without being detected, and it is not compliant with IEC 61496-2. Conduct risk assessment
analysis thoroughly before enabling this setting.
Function
Initial value
Configurable value or numerical range
Fixed Blanking
Disable
Enable/Disable
Fixed Blanking
zone
Bottom beam
1
any beam in 1-beam increments
Top beam
1
any beam in 1-beam increments
Fixed Blanking Monitoring
Lockout
Lockout/Disable monitoring/Cancel blanking zone/
Quick blanking
Number of allowable upper beams
0 beam
0 to 5 beams in 1-beam increments
Number of allowable lower beams
0 beam
0 to 5 beams (1-beam increments)
Summary of Contents for F3SG-SR Series
Page 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Page 18: ...xvi Introduction F3SG SR User s Manual...
Page 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Page 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Page 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Page 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...