320
Chapter
6
Wiring Exa
m
p
le
s
(f
or F3
SG-SR)
F3SG-SR
User’s Manual
Input/Output Circuit and Applications
6-2-1-5. Manual Reset Mode with EDM and Y-Joint Plug/Socket Connector
[Wiring Example]
• When using the Y-Joint Plug/Socket Connector (F39-GCNY2), the following functions are not available.
- External Test
- Operating Range Selection by wiring
- Wired Synchronization
• When a functional earth is necessary, wire an earth cable according to the example in
Optical Synchronization and EDM Unused
5-4-4. Functional Earth Connection
for more information.
F39-JGR3K-L and F39-JG
□
B-L
F39-GCNY2
F39-JG
A-D
24 VDC
Wiring for NPN *1
*3
24 VDC
Timing chart
F39-JGR3K-D and F39-JG
□
B-D
IN
PLC *2
KM1
KM2
M
KM1
KM2
S1
KM1
KM2
Beam state: Unblocked
Blocked
Reset switch (S)
OSSD
S1: Lockout/interlock reset switch
KM1, KM2: Safety relay with forcibly guided contacts (G7SA) or magnetic contactor
M: Motor
PLC: Programmable logic controller (Used for monitoring only. NOT related to
safety system.)
OSSD 1 (Black)
OSSD 2 (White)
24V/0V (Brown)
0V/24V (Blue)
AUX (Red)
MUTE B (Pink)
MUTE A (Gray)
RESET/EDM
(Yellow)
Receiver
Emitter
*1. Reverse the polarity of the power supply when using in the NPN system. Select a
PLC of PNP or NPN type according to the system of your application.
*2. When connecting to the PLC, the output mode must be changed with the SD
Manager 3 according to your application. Refer to
for more information on setting this function by the SD Manager 3.
*3 This is the case for a PELV circuit.
*4 Set the function with the DIP Switches on the Intelligent Tap or the SD Manager
3, restore the settings to the F3SG-SR, and perform wiring according to the
wiring diagram.
*5 To set the Short mode, set the function with the DIP Switches on the Intelligent
Tap or the SD Manager 3, restore the settings to the F3SG-SR, and perform
wiring according to the wiring diagram.
: Indicates a switch position.
Function
Setting
DIP switch
SD Manager 3
EDM *4
EDM Enabled
[External device monitoring] : Enable
Interlock *4
Manual Reset
[Start interlock] : Enable
[Restart interlock] : Enable
Operating Range Selection *5
Long (factory default setting)
Long
[Operating Range Selection] : Long mode
Non-Muting system
Perform wiring according to the wiring diagram.
N/A
[Muting] : Disable *4
External Test not used
N/A
Optical Synchronization
Connect the wires according to the diagram above.
㻟
㻻㻺
㻠
㻻㻺
㻡
㻻㻺
㻤
㻻㻺
Intelligent Tap
Needed
Summary of Contents for F3SG-SR Series
Page 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Page 18: ...xvi Introduction F3SG SR User s Manual...
Page 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Page 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Page 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Page 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...