System Operation and Functions
E
The values of T1
min
and T1
max
can be changed by the SD Manager 3.
Time t2 [ s ] for a workpiece to pass the F3SG-SR’s detection zone after passing the muting sensor A1
is:
t2 = d2 / VEquation (3)d2 [ m ] : Distance between muting sensor A1 and F3SG-SR
V [ m/s ] : Approach speed of a workpiece
Time t2 in Equation (3) must satisfy following condition:
t2 < T5Equation (4)T5: Exit-only muting delay time
The value of T5 can be changed by the SD Manager 3.
Sensors must be installed so that person’s passing should not cause the MUTING state.
Also, the muting sensors and F3SG-SR must be installed so that MUTING state caused by a
workpiece should be ended before the next workpiece arrives at the first muting sensor.
Timing chart
Workpiece
Workpiece
Workpiece
Workpiece
F3SG-SR
A1 B1
F3SG-SR
A1 B1
Hazardous zone
Hazardous zone
Moving direction
Moving direction
T1min: Muting input time limit value (minimum)
T1max: Muting input time limit value (maximum)
T2: Muting time limit
T3: Maximum allowable muting signal interruption
T4: Muting end wait time
T5: Exit-only muting delay time
T2 max.
T1min to T1max
T3 (0.1 s) max.
T1max
80 ms max. *
T3(1 s) max.
T5 max.
T4 (1 s)
* 102 ms max. when the
Intelligent Tap is connected
to the F3SG-SR.
Green blinking
Orange blinking
ON
OFF
Muting input A
(Muting sensor A1)
Muting input B
(Muting sensor B1)
Unblocked
Blocked
OSSD
ON
OFF
MUTING state
Enabled
Disabled
ON
OFF
Beam state
ABI indicator
ON
OFF
Summary of Contents for F3SG-SR Series
Page 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Page 18: ...xvi Introduction F3SG SR User s Manual...
Page 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Page 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Page 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Page 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...