1-6-3. Calculation of Response Time of Cascaded Segments
The F3SG-SR can be used in cascade connection. In cascade connection, a response time is
determined by the total number of beams.
If the total number of beams of all F3SG-SR's in a cascade connection is 12 or less, its response time
is 7 ms (Code A)/8 ms (Code B) when the Optical Synchronization is activated and 9 ms or less when
the Wired Synchronization is activated.
If the total number of beams of all F3SG-SR's in a cascade connection is 140 or less, its response time
is 12 ms (Code A)/13 ms (Code B) when the Optical Synchronization is activated and 15 ms or less
when the Wired Synchronization is activated. The number of beams of each F3SG-SR segment,
however, must be 112 or less.
If an F3SG-SR with 113 or more beams is included in the cascade connection, its response time is 17
ms (Code A)/18 ms (Code B) when the Optical Synchronization is activated and 22 ms or less when
the Wired Synchronization is activated.
The F3SG-PG cannot be used in cascade connection.
The table below summarizes the relation described above.
Cascaded sensors in Optical Synchronization with Scan Code A
*The number of beams of each sensor segment in cascaded connection must be 112 or less.
Cascaded sensors in Optical Synchronization with Scan Code B
*The number of beams of each sensor segment in cascaded connection must be 112 or less.
Cascaded sensors in Wired Synchronization
*The number of beams of each sensor segment in cascaded connection must be 112 or less.
F3SG-SRA
X
F3SG-PG-A/-L
-
F3SG-SRB
X
F3SG-PG-C
-
Number of beams
(per single sensor)
Number of beams
(total system)
Response time [ms]
ON
OFF
OFF
(Synchronized)
ON
OFF (Not
synchronized)
ON
1 to 12
1 to 12
7
35
135
1 to 112
13 to 140*
12
60
160
1 to 199
141 to 255
17
85
185
Number of beams
(per single sensor)
Number of beams
(total system)
Response time [ms]
ON
OFF
OFF
(Synchronized)
ON
OFF (Not
synchronized)
ON
1 to 12
1 to 12
8
40
140
1 to 112
13 to 140*
13
65
165
1 to 199
141 to 255
18
90
190
Number of beams
(per single sensor)
Number of beams
(total system)
Response time [ms]
ON
OFF
OFF
ON
1 to 12
1 to 12
9
45
1 to 112
13 to 140*
15
75
1 to 199
141 to 255
22
110
Summary of Contents for F3SG-SR Series
Page 1: ...Safety Light Curtain F3SG SR Series User s Manual Man No Z405I E3 01...
Page 18: ...xvi Introduction F3SG SR User s Manual...
Page 156: ...128 Chapter 2 IO Link F3SG SR User s Manual System Operation and Functions...
Page 340: ...312 Chapter 5 Cascade Connection F3SG SR User s Manual Wiring and Installation...
Page 368: ...340 Chapter 7 Maintenance Checklists F3SG SR User s Manual Checklists...
Page 398: ...370 Chapter 8 Revision History F3SG SR User s Manual Appendix...