Appendix 2 Buffer Memory Details
The following explains the details of items shown in "Buffer Memory List" (refer to
Section 3.6).
(1) Parameter information area
Stores the parameter settings.
Do not perform write to the parameter information area. Doing so may cause an
error.
The following table lists the parameter information areas.
Address
Hex. Dec.
Item Description
0
H
0 (Use
prohibited)
—
1
H
1
Number of connected
modules
Stores the total number of the slave stations that are connected to the master station
(including reserved stations).
Default value: 64 (modules)
Storage area: 1 to 64 (modules)
2
H
2
Number of retries
Stores the number of retries when a communication error occurs.
Default value: 3 (times)
Storage area: 1 to 7 (times)
3
H
3
Number of automatic
return modules
Stores the total number of the slave stations that can be returned to system operation by
a single link scan.
Default value: 1 (module)
Storage area: 1 to 10 (modules)
4
H
4
Standby master station
specification
Stores the station number of the standby master station.
Default value: 0 (no standby master station specified)
Storage area: 0 to 64 (0: No standby master station specified)
5
H
5 (Use
prohibited)
—
6
H
6
Operation specification
when CPU is down
Stores the data link status when a master station programmable controller CPU error
occurs.
Default value: 0 (Stop)
Storage area: 0 (Stop)
: 1 (Continue)
7
H
7
Scan mode
specification
Stores either the synchronous or asynchronous mode for sequence scan.
Default value: 0 (Asynchronous)
Storage area: 0 (Asynchronous)
: 1 (Synchronous)
8
H
8
Delay time setting
Set 0 for the delay time.
10
H
to 13
H
16 to 19
Reserved station
specification
Stores the reserved station.
Default value: 0 (Not specified)
Storage area: Bit corresponding to the station number turns on.
14
H
to 17
H
20 to 23
Error invalid station
specification
Stores the error invalid station.
Default value: 0 (Not specified)
Storage area: Bit corresponding to the station number turns on.
(To the next page)
Summary of Contents for L26CPU-BT
Page 1: ......
Page 2: ......
Page 32: ...3 5 3 5 3 SPECIFICATIONS ...
Page 51: ...4 2 4 2 4 PROCEDURE BEFORE OPERATION 4 ...
Page 61: ...6 4 6 4 6 INSTALLATION AND CONNECTION ...
Page 63: ...6 6 6 6 6 INSTALLATION AND CONNECTION 8 The connection method is shown below ...
Page 70: ...6 13 6 13 6 INSTALLATION AND CONNECTION ...
Page 72: ...6 15 6 15 6 INSTALLATION AND CONNECTION ...
Page 139: ...8 33 8 33 8 FUNCTIONS ...
Page 151: ...8 45 8 45 8 FUNCTIONS ...
Page 246: ...11 9 11 9 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS ...
Page 311: ...13 2 13 2 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATIONS MEMO 13 ...
Page 321: ...14 10 14 10 14 EXAMPLE OF COMMUNICATION WHEN MOUNTING MODULES ON THE HEAD MODULE ...
Page 326: ...15 5 15 5 15 TROUBLESHOOTING To the next page ...
Page 327: ...15 6 15 6 15 TROUBLESHOOTING To the next page ...
Page 328: ...15 7 15 7 15 TROUBLESHOOTING ...
Page 329: ...15 8 15 8 15 TROUBLESHOOTING 2 Troubleshooting by status logging ...
Page 436: ...App 72 App 72 APPENDIXES 7 Operating procedure of the transmission speed test ...
Page 439: ...App 75 App 75 APPENDIXES MEMO ...
Page 447: ......
Page 448: ......
Page 449: ......