App - 38 App - 38
APPENDIXES
Availability
(o: Available, x: Not available)
Online
Number Name
Description
Master station Local station
Offline
SW011F
(71F
H
)
Remote device station
initialization procedure
registration execution
individual information
(target 16)
Stores the execution information of initialization procedure
registration.
High: Next execution procedure number (FF
H
at completion)
Low: Targeted station number
8
SW0140
(740
H
)
SW0141
(741
H
)
SW0142
(742
H
)
SW0143
(743
H
)
Compatible CC-Link
ver. information
5
Indicates the slave stations compatible with CC-Link ver.2.
0: Ver.1compatible slave station
1: Ver.2compatible slave station
b15
b14
b13
b12
b3
b2
b1
b0
SW0140
SW0141
SW0142
SW0143
Numbers 1 to 64 in the above table indicate the station numbers.
16
15
14
13
4
3
2
1
48
47
46
45
36
35
34
33
32
31
30
29
20
19
18
17
64
63
62
61
52
51
50
49
to
to
to
to
to
Reserved stations and any station of the number higher than the
max. are excepted.
SW0144
(744
H
)
SW0145
(745
H
)
SW0146
(746
H
)
SW0147
(747
H
)
CC-Link ver.
installation/parameter
matching status
5
Stores the CC-Link version matching status of the parameters and
slave stations.
0: Normal
1: Matching error
Example of matching error
Installation
Ver.2compatible remote
device station
Parameter
Ver.1compatible remote
device station
Ver.1compatible remote
device station
Ver.2compatible remote
device station
b15
b14
b13
b12
b3
b2
b1
b0
SW0144
SW0145
SW0146
SW0147
Numbers 1 to 64 in the above table indicate the station numbers.
16
15
14
13
4
3
2
1
48
47
46
45
36
35
34
33
32
31
30
29
20
19
18
17
64
63
62
61
52
51
50
49
to
to
to
to
to
Reserved stations and final station number onwards are not
targeted.
SW0148
(748
H
)
Parameter mode
Indicates in which mode the system is operating.
0: Remote net ver.1 mode
1: Remote net additional mode
2: Remote net ver.2 mode
SW0149
(749
H
)
Host parameter mode
Indicates in which mode the host is operating.
0: Remote net ver.1 mode
1: Remote net additional mode
2: Remote net ver.2 mode
SW0152
(752
H
)
Max. communication
station number
Stores the maximum station number (station number of the station
number setting) that is performing data link.
1 to 64 (stations)
SW0153
(753
H
)
Number of connected
modules involved in
communication
Stores the number of modules that are performing data link.
Reserved, error invalid, and temporary error invalid stations are not
included.
SW0183
(783
H
)
Transmission speed
test result
Indicates the execution result of the transmission speed test.
0 : Normal
Other than 0: Stores an error code (refer to Section 15.3).
5: The bits for the number of occupied stations turn ON.
8: Parameter setting is required in the case of a standby master station.
(To the next page)
Summary of Contents for L26CPU-BT
Page 1: ......
Page 2: ......
Page 32: ...3 5 3 5 3 SPECIFICATIONS ...
Page 51: ...4 2 4 2 4 PROCEDURE BEFORE OPERATION 4 ...
Page 61: ...6 4 6 4 6 INSTALLATION AND CONNECTION ...
Page 63: ...6 6 6 6 6 INSTALLATION AND CONNECTION 8 The connection method is shown below ...
Page 70: ...6 13 6 13 6 INSTALLATION AND CONNECTION ...
Page 72: ...6 15 6 15 6 INSTALLATION AND CONNECTION ...
Page 139: ...8 33 8 33 8 FUNCTIONS ...
Page 151: ...8 45 8 45 8 FUNCTIONS ...
Page 246: ...11 9 11 9 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS ...
Page 311: ...13 2 13 2 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATIONS MEMO 13 ...
Page 321: ...14 10 14 10 14 EXAMPLE OF COMMUNICATION WHEN MOUNTING MODULES ON THE HEAD MODULE ...
Page 326: ...15 5 15 5 15 TROUBLESHOOTING To the next page ...
Page 327: ...15 6 15 6 15 TROUBLESHOOTING To the next page ...
Page 328: ...15 7 15 7 15 TROUBLESHOOTING ...
Page 329: ...15 8 15 8 15 TROUBLESHOOTING 2 Troubleshooting by status logging ...
Page 436: ...App 72 App 72 APPENDIXES 7 Operating procedure of the transmission speed test ...
Page 439: ...App 75 App 75 APPENDIXES MEMO ...
Page 447: ......
Page 448: ......