3 - 1 3 - 1
3 SPECIFICATIONS
3 SPECIFICATIONS
This chapter provides the specifications of the L series master/local modules.
3.1 General Specifications
For the general specifications of the L series master/local modules, refer to the
following manual.
"Safety Guidelines", the manual supplied with the CPU module or head module
3.2 Performance Specifications
The following shows the performance specifications of the L series master/local
module.
Specification
Item
Built-in CC-Link function
LJ61BT11
Transmission speed
Can be selected from 156 kbps/ 625 kbps/ 2.5 Mbps/ 5 Mbps/ 10 Mbps
Maximum overall cable distance
(Maximum transmission distance)
Varies according to the transmission speed (Refer to Section 3.2.2)
Maximum number of connected stations
(master station)
64 (Refer to Section 3.2.1)
Number of occupied stations
(local station)
1 to 4 stations
The number of stations can be switched by GX Works2 parameter setting.
Remote I/O (RX, RY)
: 2048 points
Remote register (RWw) : 256 points
(master station
remote device station/local station/ intelligent
device station/standby master station)
Maximum number of link points per system
1
Remote register (RWr)
: 256 points
(remote device station/local station/ intelligent device station/standby
master station
master station)
Remote I/O (RX, RY)
: 32 points
(local station is 30 points)
Remote register (RWw) : 4 points
(master station
remote device station/local station/ intelligent
device station/standby master station)
Number of link points per station
1
(remote station/local station/intelligent device
station/standby master station)
Remote register (RWr)
: 4 points
(remote device station/local station/ intelligent device station/standby
master station
master station)
Communication method
Broadcast polling method
Synchronous method
Frame synchronization method
Encoding method
NRZI method
Transmission path
Bus (RS-485)
Transmission format
Conforms to HDLC
Error control system
CRC (X
16
+ X
12
+ X
5
+ 1)
Connection cable
Ver.1.10 compatible CC-Link dedicated cable
RAS function
Automatic return function
Slave station cut-off function
Error detection by the link special relay/register
Number of occupied I/O points
32 points (I/O assignment: Intelligent 32 points)
5V DC internal current consumption
2 0.46A
Weight
2 0.15kg
1 Indicates the number of link points in remote net ver.1 mode. For the number of link points in remote net
Ver.2 mode and remote net additional mode, refer to Section 3.2 (1).
2 For the 5V DC internal current consumption and weight, refer to the following manual.
MELSEC-L CPU Module User's Manual (Hardware Design, Maintenance and Inspection)
3
Summary of Contents for L26CPU-BT
Page 1: ......
Page 2: ......
Page 32: ...3 5 3 5 3 SPECIFICATIONS ...
Page 51: ...4 2 4 2 4 PROCEDURE BEFORE OPERATION 4 ...
Page 61: ...6 4 6 4 6 INSTALLATION AND CONNECTION ...
Page 63: ...6 6 6 6 6 INSTALLATION AND CONNECTION 8 The connection method is shown below ...
Page 70: ...6 13 6 13 6 INSTALLATION AND CONNECTION ...
Page 72: ...6 15 6 15 6 INSTALLATION AND CONNECTION ...
Page 139: ...8 33 8 33 8 FUNCTIONS ...
Page 151: ...8 45 8 45 8 FUNCTIONS ...
Page 246: ...11 9 11 9 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS ...
Page 311: ...13 2 13 2 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATIONS MEMO 13 ...
Page 321: ...14 10 14 10 14 EXAMPLE OF COMMUNICATION WHEN MOUNTING MODULES ON THE HEAD MODULE ...
Page 326: ...15 5 15 5 15 TROUBLESHOOTING To the next page ...
Page 327: ...15 6 15 6 15 TROUBLESHOOTING To the next page ...
Page 328: ...15 7 15 7 15 TROUBLESHOOTING ...
Page 329: ...15 8 15 8 15 TROUBLESHOOTING 2 Troubleshooting by status logging ...
Page 436: ...App 72 App 72 APPENDIXES 7 Operating procedure of the transmission speed test ...
Page 439: ...App 75 App 75 APPENDIXES MEMO ...
Page 447: ......
Page 448: ......
Page 449: ......